Experiment Research of Recycle the CondensateWater of Split Air-conditioner
Author:
Affiliation:

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    针对分体空调冷凝水的浪费和无规律排放,回收冷凝水用于预冷冷凝器进风具有实际的节能潜力,笔者通过制作的一套冷凝水回收预冷装置,将该装置应用于某实验室单体空调,并进行了3种工况下的试验测试,分别为未装预冷装置、提供足够冷水预冷装置,以及空调器提供自身冷凝水预冷装置。计算和分析结果表明装有预冷装置前后,无论提供足够冷水还是自身产生的冷凝水,其性能系数COP分别提高了12.94%和9.52%。同时发现冷凝水产生量与需水量具有一定的差距,仅为需水量的56.26%。最后,结合试验现状和结果,对该预冷装置的应用和推广给出了相应的建议。

    Abstract:

    In allusion to waste and irregularity emissions of the condensate water of split air-conditioner,with the actual energy saving potential to recycle the condensate water use for precool the inlet air of condenser, the author by means of make a device to recycle and precool the condensate water, then apply this device to split air-conditioner of a laboratory, and experiments are conducted. The computation and analysis results showed that before and after equipped with the precooled device, COP of the conditioner increasing 12.94% and 9.52% respectively under the conditions which applying sufficient cold water or produced condensate water by itself. Meanwhile, a certain gap of quantity between the produced condensate water and the cool water demanded was discovered, the former only account to 56.26% of the latter. In the end, combine the experiment condition and results to give some corresponding suggestions so as to the application and popularization of the precooled device.

    参考文献
    相似文献
    引证文献
引用本文

陈鹏,卢军,张惠民,霍侦侦,曾潇.分体空调冷凝水回收利用实验研究[J].土木与环境工程学报(中英文),2012,34(Z2):169-172. CHEN Peng, LU Jun, ZHANG Hui-min, HUO Zhen-zhen, ZENG Xiao. Experiment Research of Recycle the CondensateWater of Split Air-conditioner[J]. JOURNAL OF CIVIL AND ENVIRONMENTAL ENGINEERING,2012,34(Z2):169-172.[doi]

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期: 2013-03-07
  • 出版日期:
文章二维码