冬季空调不加湿对室内参数的影响
CSTR:
作者:
中图分类号:

TU831.3

基金项目:

国家自然科学基金(51366005、51066002)


Humidity analysis of air-conditioned rooms without humidification in winter
Author:
  • 摘要
  • | |
  • 访问统计
  • |
  • 参考文献 [15]
  • |
  • 相似文献
  • | | |
  • 文章评论
    摘要:

    基于质量守恒方程导出了冬季空调系统不加湿时房间内的含湿量计算式,综合考虑影响室内含湿量的主要因素,得出冬季空调可以不加湿时应满足的条件,考察了中国典型气候区代表性空调房间冬季空调不加湿时室内相对湿度能否满足设计要求。研究表明:中国各地区的商场,夏热冬冷地区的餐厅及三星级及以下酒店多功能厅,夏热冬暖地区的影剧院、办公室、酒店客房及多功能厅、餐厅,温和地区的办公室、三星级及以下酒店客房、酒店多功能厅及餐厅空调系统不加湿即可达到设计湿度要求;严寒地区及寒冷地区的影剧院、办公室、酒店客房、酒店多功能厅及餐厅,夏热冬冷地区的影剧院、办公室、酒店客房、四星级及以上酒店多功能厅以及温和地区的影剧院、四星级及以上酒店客房等房间的空调系统必须加湿才能达到设计要求。

    Abstract:

    Based on the mass conservation equation, the calculation formula of the moisture content in the air-conditioned room without humidification in winter are deduced. Synthetically considering major influencing factors of the indoor moisture content, the criterion used to estimate the relative humidity of air-conditioned rooms without humidification in winter are established. Furthermore, the relative humidity in typical air-conditioned rooms without humidification in typical climate regions in winter is checked against the criterion. The main conclusions are as follows:the relative humidity of air-conditioned supermarket all around our country, restaurants and the multi-purpose halls of 3-star and below 3-star hotel in the "hot summer and cold winter" climatic region, movie theaters,office, the bedrooms and multi-purpose halls of hotel, restaurants in the "hot summer and warm winter" climatic region, and office, the bedrooms of 3-star and below 3 star hotel, the multi-purpose halls of hotel and restaurants in the "mild" climatic region can meet the required value without humidification. But, the relative humidity of air-conditioned movie theaters, office, the bedrooms and multi-purpose halls of hotel and the restaurants in the "cold" and "severe cold" climatic region, movie theaters, office, the bedrooms of hotels, and the multi-purpose halls of 4 star and over 4 star hotels in the "hot in summer and cold in winter", and movie theaters, the bedrooms and multi-purpose halls of 4-star and over 4-star of hotels in the "mild" climatic region can not meet the required value without humidification.

    参考文献
    [1] 袁萌,王彦淞.室内空气温湿度对人体热舒适性影响的实验研究[J].建筑节能,2014(8):17-20. YUAN M,WANG Y S.Experimental research on impact of indoor air temperature and humidity on Human thermal comfort[J].Building Energy Efficiency,2014(8):17-20.(in Chinese)
    [2] 徐昆仑.低湿对人体舒适感影响的实验研究[D].重庆:重庆大学,2016:17-19. XU K L.Effect of low air humidity on human comfort sensation[D].Chongqing:Chongqing University,2016:17-19.(in Chinese)
    [3] 李金梅,朱鸣,李强,等.环境温湿度对人体静电电位影响的实验研究[J].消防科学与技术,2014(12):1370-1373. LI J M,ZHU M,LI Q,et al.Experimental study on human body electrostatic potential effect by environmental temperature and humidity[J].Fire Science and Technology,2014(12):1370-1373.(in Chinese)
    [4] 任召峰.静电危害及防护[J].现代电子技术,2010,33(21):203-206. REN Z F.Damage and prevention of static electricity[J].Modern Electronics Technique,2010,33(21):203-206.(in Chinese)
    [5] 严汉彬,丁力行.控制空调系统微生物污染的温湿度条件分析[J].制冷与空调,2011,11(2):14-17. YAN H B,DING L X.Analysis of conditions of temperature and humidity to control microbial contaminant in air-conditioning system[J].Refrigeration and Air-Conditioning,2011,11(2):14-17.(in Chinese)
    [6] 刘乃玲,蔡芳芳,吕金全.风机盘管湿膜加湿器对房间温湿度影响的实验研究[J].山东建筑大学学报,2012,27(2):147-151. LIU N L, CAI F F, LV J Q. Experimental re search on the influence of room temperature and relative humidity by fan coil unit with wet film humidifier[J]. Journal of Shandong Jianzhu University, 2012, 27(2):147-151.(in Chinese)
    [7] 宋阳光,吴志湘,王谦.传统常用空调系统冬季新风处理的分析与研究[J].发电与空调,2015(3):40-43. SONG Y G,WU Z X,WANG Q.Fresh air processed analysis and studies for common air condition system[J]. Refrigeration Air Conditioning & Electric Power Machinery,2015(3):40-43.(in Chinese)
    [8] GHAZIKHANI M, KHAZAEE I,VAHIDIFAR S. Energy analysis of two humidification process methods in air-conditioning systems[J].Energy and Buildings,2016,124:129-140.
    [9] SOBRINHO P M,TUNA C E.Experimental research on the influence of the air humidity conditions in an air conditioning system[J].Experimental Thermal and Fluid Science,2013,49:152-159.
    [10] CHAUHANS S,RAJPUT S P S. Thermodynamic analysis of the evaporative-vapor compression based combined air conditioning system for hot and dry climatic conditions[J].Journal of Building Engineering,2015(4):200-208.
    [11] ZHANG J Y, GE T S, DAI Y J,et al.Experimental investigation on solar powered desiccant coated heat exchanger humidification air conditioning system in winter, Energy[S]. 2017, ISSN 0360-5442,
    [12] 陆耀庆.实用供热空调设计手册[M].2版.北京:中国建筑工业出版社,2008:1547-1548. LU Y Q.Practical heating air conditioning design manual[M].2ed edition. Beijing:China Architecture & Building Press,2008:1547-1548.(in Chinese)
    [13] PICARD A, DAVIS R S, GLÄlSER M, et al. Revised formula for the density of moist air (CIPM-2007)[J]. Metrologia, 2008, 45(2):149.
    [14] 章霆芳,章伯其.湿空气饱和水蒸气压力与温度关系式的改进与应用[J].发电与空调,2005,26(4):43-45. ZHANG T F,ZHANG B Q.Improvement and application of the relationship between the water vapor saturation pressure and temperature of the moist air[J].Refrigeration Air Conditioning & Electric Power Machinery,2005,26(4):43-45.(in Chinese)
    [15] 中华人民共和国住房和城乡建设部. 民用建筑供暖通风与空气调节设计规范:GB 50736-2012[S]. 北京:中国建筑工业出版社,2012:6-13. Ministry of Housing and Urban-Rural Development of the People Republic. Design code for heating ventilation and air conditioning of civil buildings:GB 50736-2012[S]. Beijing:China Architecture & Building Press,2012:6-13.(in Chinese)
    相似文献
    引证文献
    网友评论
    网友评论
    分享到微博
    发 布
引用本文

赵玲玲,王辉涛,秦进,葛众,韩金蓉.冬季空调不加湿对室内参数的影响[J].土木与环境工程学报(中英文),2018,40(4):63-70. Zhao Lingling, Wang Huitao, Qin Jin, Ge Zhong, Han Jinrong. Humidity analysis of air-conditioned rooms without humidification in winter[J]. JOURNAL OF CIVIL AND ENVIRONMENTAL ENGINEERING,2018,40(4):63-70.10.11835/j. issn.1674-4764.2018.04.010

复制
分享
文章指标
  • 点击次数:875
  • 下载次数: 976
  • HTML阅读次数: 420
  • 引用次数: 0
历史
  • 收稿日期:2017-09-25
  • 在线发布日期: 2018-07-05