Effect of fiber orientation on the mechanical properties of reactive powder concrete members
Author:
Affiliation:

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    为研究准静态荷载下纤维分布对活性粉末混凝土(RPC)构件力学性能的影响,对同一纤维掺量(2%)下不同纤维长度(13~20 mm)的单向分布和乱向分布钢纤维RPC试件开展了四点受弯试验。通过选取弯拉荷载挠度曲线上的初裂点、峰值点及其他几个特征点,定量分析单向分布和乱向分布钢纤维RPC的弯拉性能。结果表明:钢纤维在主拉应力方向上的方向系数显著影响基体的弯曲性能。其中,较乱向分布试件,单向分布钢纤维试件的弯拉峰值应力、弯曲韧性均大幅提高,且跨中挠度达到L/150时,残余强度仍比初裂强度高4.35~16.9 MPa;纤维长度由13 mm增加至20 mm时,与乱向分布试件相比,单向分布试件的裂后弯曲性能提高幅度更明显,且单向分布试件受荷越大,纤维长径比的优势越显著;单向分布试件断口处纤维分布均匀,绝大部分方向与主裂纹方向垂直,锚固长度大,断口处桥接效应显著;综合考虑单向钢纤维RPC试件的等效弯曲应力、耗能能力等指标,在纤维掺量为2%、纤维长度为20 mm时,其力学性能最优。

    Abstract:

    To study the influence of fiber distribution on the mechanical properties of Reactive Power Concrete(RPC) members under quasi-static loading, the four-point bending test was carried out on aligned steel fiber RPC and steel fiber RPC specimens at the same fiber content (2%) and different fiber lengths (13~20 mm).By selecting the initial crack point, peak point and other characteristic points on the bending load-deflection curves, the bending properties of aligned steel fiber RPC(ASFRPC) and steel fiber RPC(SFRPC) were analyzed quantitatively. The experimental results show that orientation coefficient of steel fibers in the direction of main tensile stress has a strong impact on the deflection hardening behavior in bending. First of all, the bending tensile peak stress and bending ductility of ASFRPC is greater than that of SFRPC.In particular, when the mid-span deflection reaches L/150, the residual strength of ASFRPC specimen is still 4.35~6.9 MPa higher than that of the initial crack strength.Secondly, when the fiber length increases from 13 mm to 20 mm, the flexural property of ASFRPC specimen improves more significantly than that of SFRPC specimen, and the advantage of fiber length diameter ratio is more significant with the increasing load of ASFRPC specimen. Thirdly, the fiber distribution of ASFRPC is uniform at the fracture, most of which are perpendicular to the main crack direction.Besides, the anchorage length is also long, and the bridging effect is significant at the fracture. In conclusion, considering the equivalent bending stress and energy absorption capacity of ASFRPC specimens, the mechanical properties of aligned steel fiber specimens perform best when the fiber content is 2% and the fiber length is 20 mm.

    参考文献
    相似文献
    引证文献
引用本文

李坤坤,杨克家,李坤梁,林一苇.纤维分布对活性粉末混凝土构件力学性能的影响[J].土木与环境工程学报(中英文),2022,44(5):197-204. LI Kunkun, YANG Kejia, LI Kunliang, LIN Yiwei. Effect of fiber orientation on the mechanical properties of reactive powder concrete members[J]. JOURNAL OF CIVIL AND ENVIRONMENTAL ENGINEERING,2022,44(5):197-204.10.11835/j. issn.2096-6717.2020.197

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2020-08-31
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期: 2022-06-28
  • 出版日期: