地下地铁车站屏蔽门渗入风量计算模型
CSTR:
作者:
作者单位:

1.重庆大学 土木工程学院;2.重庆大学 国家级低碳绿色建筑国际联合研究中心;3.重庆大学 绿色建筑与人居环境营造国际合作联合实验室;4.重庆大学 风工程及风资源利用重庆市重点实验室,重庆 400045

作者简介:

高志宏(1997- ),男,主要从事地铁站环控系统节能研究,E-mail:928550381@qq.com。
GAO Zhihong (1997- ), main research interest: energy efficiency of environment control system in subway,E-mail: 928550381@qq.com.

通讯作者:

刘猛(通信作者),男,教授,博士生导师,E-mail:liumeng2033@126.com。

中图分类号:

TU831.2

基金项目:

重庆市高校创新研究群体(CXQT21004);重庆市建设科技项目(城科字2021第3-10)


A calculation model of infiltration air volume of platform screen doors in subway station
Author:
Affiliation:

1.School of Civil Engineering, Chongqing UniversityChongqing;2.National Center for International Research of Low-carbon and Green Building, Chongqing UniversityChongqing;3.Joint International Research Laboratory of Green Building and Built Environment, Chongqing UniversityChongqing;4.Chongqing Key Laboratory of Wind Engineering and Wind Energy Utilization, Chongqing University, Chongqing 400045, P. R. China

Fund Project:

University Innovation Research Group of Chongqing (No. CXQT21004); Construction Science andTechnology Projects of Chongqing (No. 2021-3-10)

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    屏蔽门渗透风量是影响地铁车站冷负荷的重要因素。提出一种屏蔽门渗透风量计算模型,基于测试风速分析,对屏蔽门单周期渗透风量进行量化,分不同位置和不同阶段研究屏蔽门渗透风的特征,通过对列车运行因素进行分析,建立一种屏蔽门渗透总风量的计算方法,以期对地铁车站的设计计算及运营等工作提供借鉴。结果表明:不同位置屏蔽门的渗透风速不同,沿着列车的运行方向,屏蔽门单周期渗透风速和风量都随门位置的变化而减小,出站侧的屏蔽门单周期渗入风量约为进站侧的65%;不同阶段屏蔽门渗透风量也存在差异,列车停靠阶段单周期渗透风量最大,为进站阶段的10倍左右;确定了屏蔽门单周期渗透风量的范围,并提出相应的计算模型,据此计算得到地铁车站屏蔽门全天的渗透风量。

    Abstract:

    The infiltration air volume of platform screen doors (PSD) is an important factor affecting the cooling load of subway station. This paper proposes a calculation model of infiltration air volume of PSD. Based on the analysis of test wind speed, the single cycle PSD infiltration air volume is quantified, and the characteristics of infiltration air volume of PSD are studied in different positions and stages. Then, through the analysis of train operation factors, a calculation method of total infiltration air volume of PSD is established, in order to provide reference for the design and operation of subway station. The results show that: (1) the infiltration wind speed of PSD at different positions is different. Along the running direction of the train, the infiltration wind speed and air volume of PSD in a single cycle decrease with the change of door position. The single cycle infiltration air volume of PSD at the exit side is about 65% of that at the entrance side. (2) There are also differences in the infiltration air volume of PSD in different stages. The total infiltration air volume in a single cycle in the train stopping stage is the largest, which is about 10 times that in the train arrival stage. (3) The range of infiltration air volume of single cycle PSD is given, which provides a basis for the calculation of total infiltration air volume, and the corresponding calculation model is proposed, which can calculate the whole day air volume of PSD penetration of subway station.

    参考文献
    相似文献
    引证文献
引用本文

高志宏,刘猛,李子桥,向世曦,胡梦强.地下地铁车站屏蔽门渗入风量计算模型[J].土木与环境工程学报(中英文),2023,45(3):126-133. GAO Zhihong, LIU Meng, LI Ziqiao, XIANG Shixi, HU Mengqiang. A calculation model of infiltration air volume of platform screen doors in subway station[J]. JOURNAL OF CIVIL AND ENVIRONMENTAL ENGINEERING,2023,45(3):126-133.10.11835/j. issn.2096-6717.2022.036

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2022-02-09
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期: 2023-04-29
  • 出版日期:
文章二维码