一次泵空调冷水系统的水力特性与节能分析
作者:
作者单位:

作者简介:

通讯作者:

中图分类号:

基金项目:

国家“十一五”科技支撑计划重大项目(2006BAJ02A09);国家自然科学基金重点项目(50838009);重庆大学研究生科技创新基金项目(CDJXS10210004)


Hydraulic Characteristics and Energy Efficiency of An Air Conditioning Chilled Water System With Primary Pumps
Author:
Affiliation:

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    以一次泵空调冷水系统为研究对象,针对其水力特性与节能方式进行了理论分析。结果表明:末端为空调机的一次泵水系统易出现大温差小流量的情况,而末端为空调机与风机盘管组合形式的系统易出现小温差大流量情况。在冷负荷减少时,为更好的确保一次泵空调冷水系统节能运行,采用定水量系统调节冷水机组出口水温时应减少水系统的旁通水量;采用水泵变频调节且水泵所占空调水系统能耗比大于0.3,当系统的水力特性越接近末端为空调机形式的水力特性时,采用水泵变频调节效果越好(节能率大于10%)。在采用调节冷水机出水温度和变频调节冷水量匹配冷负荷时,冷水过量情况仍然存在,需旁通水量,水泵定频和变频时,可分别根据单台冷水机水流量的1.2~1.8、0.2~1倍来选择旁通管径。

    Abstract:

    The hydraulic characteristics and energy-saving performance of a chilled water system with primary pumps is analyzed. It is proved that the hydraulic characteristics of the system with terminal of the air conditioners tends to large temperature differences and small flow rate, while the hydraulic characteristics of the system with terminal of the combination of fan coil units and air conditioners tends to large flow rate and small temperature differences. When the cooling load is reduced, in order to ensure the energy-saving performance of the primary pump system, the fixed chilled water flow is required. If the fixed water flow system is adopted to regulate the outlet water temperature,the bypass water flow rate should be decreased as much as possible. If the pump frequency regulation is selected, and the proportion of energy consumption of the pump accounts for 30% of the total at the same time, the more the system’s hydraulic characteristics approaches that of air conditioners, the higher the energy-saving rate will be, which could be markedly greater than 10%. By regulating the water temperature and cold water quantity, over flow of chilled water still exists. Therefore, bypass water flow should be provided. And the bypass pipe diameter is determined respectively by the water flows which are 1.2 ~ 1.8 or 0.2 ~ 1.0 times larger than that of a single chiller when the pump works in frequency conversion and constant frequency.

    参考文献
    相似文献
    引证文献
引用本文

高亚锋,李百战,陈玉远,刘晓庆,金振星.一次泵空调冷水系统的水力特性与节能分析[J].土木与环境工程学报(中英文),2010,32(6):100-104. GAO Ya-feng, LI Bai-zhan, CHEN Yu-yuan, LIU Xiao-qing, JIN Zhen-xing. Hydraulic Characteristics and Energy Efficiency of An Air Conditioning Chilled Water System With Primary Pumps[J]. JOURNAL OF CIVIL AND ENVIRONMENTAL ENGINEERING,2010,32(6):100-104.10.11835/j. issn.1674-4764.2010.06.017

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2010-05-18
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期:
  • 出版日期: