住宅辐射-送风末端冷负荷分担率研究——从热舒适及室内空气品质角度
作者:
作者单位:

作者简介:

通讯作者:

中图分类号:

基金项目:

“十一·五”国家科技支撑计划重大项目(2006BAJ01A05;2006BAJ01B05);中央高校基本科研业务费专项资金(CHD2010JC025);长安大学基础研究支持计划专项资金;干旱、半干旱地区水资源与国土环境实验室开放基金


Sharing Rate of Cooling Load of Radiant Terminal Device and Air Supply Terminal Device in Residential Buildings——From the Perspective of Thermal Comfort and Indoor Air Quality
Author:
Affiliation:

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    以住宅建筑为研究对象,针对低、中、高负荷3种不同住宅负荷工况,对不同冷负荷条件下不同负荷分担率下的室内热环境进行了数值模拟,分别分析比较不同冷负荷分担率匹配时室内热舒适性水平及室内空气品质情况,从舒适和健康的角度,分析适宜的冷负荷分担率范围。研究结果表明辐射供冷末端承担的显热负荷分担率ωc<07时,可将工作区人体热舒适性指标控制在舒适性标准允许范围内。从避免局部不舒适度方面讲,ωc宜取04~1。从室内空气品质角度讲,定风量模式低中负荷工况,ωc宜取05~09,高负荷工况,ωc宜取035~06;变风量模式,ωc值越小,室内空气品质越好。

    Abstract:

    Taking residential buildings as the study objects, for three different residential load types such as low load, medium load, and high load type, indoor thermal environments of different load sharing-rates are simulated, respectively. Indoor thermal comfort and indoor air quality of different load sharing-rates are also analyzed and evaluated. And the appropriate range of cooling load sharing-rates are given from the view of both occupants thermal comfort and occupants health. When ωc (the sensible heat load sharing rate of the radiant terminal device) <0.7, the human thermal index in work region can be controlled within the range of thermal comfort standard. From the point of avoiding local discomfort, ωc is suggested to take 04~1. As regard to indoor air quality, for the constant air volume mode, ωc is suggested to take 0.5~0.9 under low and middle load conditions, and ωc is suggested to take 0.35~0.6 under high load conditions. For the variable air volume mode, the smaller the value of ωc is, the better indoor air quality is.

    参考文献
    相似文献
    引证文献
引用本文

隋学敏,张旭.住宅辐射-送风末端冷负荷分担率研究——从热舒适及室内空气品质角度[J].土木与环境工程学报(中英文),2011,33(5):114-120. SUI Xue-min, ZHANG Xu. Sharing Rate of Cooling Load of Radiant Terminal Device and Air Supply Terminal Device in Residential Buildings——From the Perspective of Thermal Comfort and Indoor Air Quality[J]. JOURNAL OF CIVIL AND ENVIRONMENTAL ENGINEERING,2011,33(5):114-120.10.11835/j. issn.1674-4764.2011.05.019

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期:
  • 出版日期: