毛细管网供冷室内环境对比实验研究
梁秋锦1, 陈金华2, 段坤林3, 孙海1, 韩浩然1, 宋静2
1.重庆鲁能英大置业有限公司, 重庆 400060;2.重庆大学 城市建设与环境工程学院, 重庆 400045;3.重庆市设计院, 重庆 400015
摘要:
在18℃供水温度下,对重庆地区毛细管网辐射供冷系统进行实验测试,分析了毛细管网顶棚、墙面、地面3种敷设方式的室内热工参数。结果表明:毛细管网顶棚、墙面、地面3种敷设方式供冷稳定时,人员活动区的平均温度依次为26.27、27.22、26.57℃,辐射表面平均温度依次为20.96、21.14、22.76℃,PMV依次为-0.27、0.32、-0.2,PPD依次为7.06%、7.47%、6.34%。在实验条件下,3种敷设方式供冷时室内温度均能满足≤ 28℃的要求,PMV、PPD均能满足《民用建筑室内热湿环境评价标准》(GB/T50785-2012)Ⅰ级热舒适评价指标。
关键词:  毛细管网  辐射供冷  敷设位置  室内环境
DOI:10.11835/j.issn.2096-6717.2019.087
分类号:TU831
基金项目:国家重点研发计划(2016YFC0700303)
Comparative experimental analysis of capillary radiant cooling on indoor environment
Liang Qiujin1, Chen Jinhua2, Duan Kunlin3, Sun Hai1, Han Haoran1, Song Jing2
1.Chongqing Luneng Yingda Real Estate Co., Ltd, Chongqing 400060, P. R. China;2.Faculty of Urban Construction and Environmental Engineering, Chongqing University, Chongqing 400045, P. R. China;3.Chongqing Architectural Design Institute Chongqing 400015 P. R. China
Abstract:
Tests of capillary radiant cooling system in Chongqing were carried out and thermal parameter were analyzed in conditions of three different capillary laying modes (ceiling, wall and floor) with 18℃ supply water temperature. It concluded that when capillaries were laid on the ceiling, wall and floor respectively, the average temperature of working area was 26.27, 27.22 and 26.57℃ respectively and the radiation surface temperature was 20.96, 21.14 and 22.76℃ in turn. By calculation, the PMV of three conditions was -0.27, 0.32 and -0.2 PPD results were 7.06%, 7.47% and 6.34% respectively. It illustrated that all three laying ways at this experimental conditions could meet the air temperature requirements (no more than 28℃) and PMV, PPD attain thermal environment category I.
Key words:  capillary  radiant cooling  laying way  indoor environment