    This paper is a comprehensive report about the research of high efficient energy-saving ammonia air cooler. In the paper, it is introduced that the test of two-side long V-groove finned pipes which are fit for the evaporators of ammonia air coolers, optimum experiments of the finned pipes, and field experiments of contrasting the model machine with the old one in a cold storage. The result shows that the air-side heat transfer performance coefficient and the overall heat transfer performance coefficient of the two-side optimum long V-groove finned pipes are higher from 18.25% and 12.85% than those of conven tional rectangular plain-plate finned pipes respectively. At last, it is introduced the structure design of the high efficient energy-saving air cooler. Used by a few of units, it is proved that this type of air cooler has characteristics of compact structure, less floor area occupied, high heat transfer efficiency, convenient maintenance and management, and is of notable economical effect.

    Reference
    Related
    Cited by
Get Citation

刘宪英,李盛和,黄振夷,王厚华,卢军.氨高效节能冷风机研究[J].土木与环境工程学报(中英文),1992,14(4):