Abstract:Four series stud push-out specimens were conducted to study static mechanical behavior when stud shear connectors of composite beams were corroded. Firstly, the studs were manually rapidly corroded by electrochemical methods, and then a static load test was performed on them. Test results show that when corrosion occurs at stud rod especially close to combined surface, the ultimate bearing capacity reduces most by 18%, slip under the same load increases, and slip relative to the ultimate load reduces most by 12%. When corrosion occurs at the large end of stud, it has little effect on ultimate bearing capacity of push-out specimens, but deformation performance of stud shear connectors is affected seriously.