    A new composite structure which is composed of steel beam and concrete girder is introduced in fuel electric plant construction. With different height of concrete girders with or without anchor bar, two scale models from an actual project were designed and tested. It is shown that the maximum restraining moment of ends of steel beams is approximately 60kN*m; influence of anchor bar is little; the one with 600mm high concrete beam is damaged by shear, and the others steel beam is damaged by bending failure. Finite element models were built for supplementary analysis, and the result indicates that critical value of the height of concrete beam of different failure modes is 700mm; stiffness of shear key and thickness of floor have great influence on the structure; size of anchor bar has little influence; and width of the end of the steel beam has certain influence.

    Reference
    Related
    Cited by
Get Citation

余江滔,廖杰洪,陆洲导,周运瑜.插入式钢次梁节点试验与有限元分析[J].土木与环境工程学报(中英文),2012,34(6):13~18