Modeling and Experimental Analysis on CO2 Heat Pump in Low Temperature Ambient
Author:
Affiliation:

Clc Number:

Fund Project:

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
  • |
  • Comments
    Abstract:

    The use of CO2 air-source heat pump for heating feasibility in low temperature was analyzed. A static simulation model for the CO2 heat pump was developed, and component models of the gas cooler, evaporator, compressor and expansion valve were constructed with careful consideration of the heat transfer performances. To validate the simulation model, experiments were carried out with an actual CO2 heat pump system for heating. By comparing the simulated and experimental data, the effects of the inlet water temperature and outside air temperature on the characteristics of the system were discussed. Furthermore, an analysis on the effect of a recuperator on the performance of the system was analyzed. It is shown that when the outside temperature is -20℃, the COPh is 2.25, which indicates that this system works well in low temperature, and the efficiency of system COPh is improved by 5% when recuperator is used.

    Reference
    Related
    Cited by
Get Citation

袁磊,余南阳.低温环境下CO2空气源热泵系统模型及实验研究[J].土木与环境工程学报(中英文),2012,34(6):133~138