Mathematical Model and Operation Analysis of Semi-submerged Rotary Orifice Sewage Source Heat Pump Intake Machine
CSTR:
Author:
Affiliation:

Clc Number:

Fund Project:

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
  • |
  • Comments
    Abstract:

    To solve the flow instability and adjustment difficulty of filtering dirt-removing device in the sewage source heat pump system, which affect the efficiency of heat exchanger, semi-flooded rotary orifice sewage auto-strainer was generated. According to establishing the mathematical model, the effect is analysed of pollutant concentration and liquid level height of sewage and rotation period of orifice plate to filtered flow rate, filtered load and filtering surface block coefficient. The result shows that: in the certain condition of sewage liquid level height and orifice plate rotation period, the increase of sewage will decrease the filtered flow rate of orifice plate, and increase filtering surface block coefficient; The effect of pollutant concentration change in the sewage to orifice plate filtered flow rate could be adjusted by regulating the sewage liquid level height and orifice plate rotation period, and the moderating effect of orifice plate rotation period is better than that of sewage liquid level height.