Applicability of temperature difference control mode for variable chilled water flow systems
CSTR:
Author:
Affiliation:

Clc Number:

Fund Project:

Special Funds for Technical Development Research of Scientific Research Institutes (No.2009EG131249); National Science and Technology Support Plan (No. 2014BAJ02B01)

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
  • |
  • Comments
    Abstract:

    The hydraulic characteristics of the variable primary flow system with on-off valves under temperature difference control is investigated, and the nonlinear heat exchange coupling property of fan coil units and rooms is combined to further explore the applicable conditions of temperature difference control and setting procedures of temperature difference value(TDV). The result indicates that the temperature difference control in the system with on-off valves at the terminal is also applicable when the pipe network's load is equally distributed and the load changing rule of each opening user is similar. In this case, the system's hydraulic disorder has smaller impact on the indoor temperature and humidity. When adopting variable temperature difference control, setting TDV piecewise according to different total load rates cannot have good control of indoor temperature and humidity. Therefore, it is recommended to set TDV according to ensure fan coil's dehumidification capacity and indoor dry-bulb temperature preferentially, compared with current methods, the stability of indoor temperature can be guaranteed under the same fluctuation of the indoor relative humidity.

    Reference
    Related
    Cited by
Get Citation

陈峰,刘金祥,李沁,陈晓春.变流量冷冻水系统温差控制法的适用性[J].土木与环境工程学报(中英文),2015,37(3):94~101

Copy
Share
Article Metrics
  • Abstract:
  • PDF:
  • HTML:
  • Cited by:
History
  • Received:January 09,2015
  • Revised:
  • Adopted:
  • Online: July 09,2015
  • Published:
Article QR Code