Bearing capacity of steel tube-concrete-FRP-concrete composite columns
CSTR:
Author:
Affiliation:

Clc Number:

Fund Project:

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
  • |
  • Comments
    Abstract:

    The sectional form of steel-concrete-FRP-concrete (SCFC) column, as a novel composite column, has a steel tube as the outer layer and a circular FRP tube as the inner layer, and concrete filled between these two layers and within the FRP tube. Considering the confinements from both outer steel and inner FRP layers, the twin shear unified strength theory and force equilibrium condition are utilized to develop an analytical model of bearing capacity of SCFC column. The accuracy of the proposed model is evidenced through being compared with experimental data. The parametrical study is conducted in order to evaluate the confinements affected by the sectional steel proportion, ratio of FRP to steel, ratio of diameter to thickness of FRP and FRP diameter itself. The results indicate that the greater sectional steel proportion, the larger ratio of FRP to steel, and smaller ratio of diameter to thickness of FRP have positive contributions on the confinements of SCFC. The ratio of FRP diameter to steel side length locates between 0.65-0.75 can lead to a better confinement.

    Reference
    Related
    Cited by
Get Citation

陶毅,张海镇,史庆轩,陈建飞.内置FRP约束混凝土的方钢管混凝土轴压承载力[J].土木与环境工程学报(中英文),2017,39(2):43~49