Effect of multi factor on H2S and NH3 concentration in underground wastewater treatment plants
CSTR:
Author:
Affiliation:

Clc Number:

X512

Fund Project:

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
  • |
  • Comments
    Abstract:

    With experiment test, a second-order orthogonal experiment was carried out to analyze the weight of factors affecting H2S and NH3 concentration in sludge dewatering of underground wastewater treatment plants:temperature, humidity and exhaust volume, and according to pollution level and energy consumption, a comprehensive evaluation index was put forward. The results indicate that Interaction between temperature and exhaust volume is important to H2S and NH3 concentration (p<0.05). When the outdoor temperature is 20℃, the H2S and NH3 concentration of the dewatering machine room is the lowest. It is reduced by 2.5 times compared with 35℃. According to the comprehensive evaluation index, the minimum K value is 4.5 in the ventilation frequency of 2.7. Below 2.7 times of ventilation, the odor concentration is too high, and the energy consumption is too large when higher than the 2.7 times of ventilation. Therefore, the most appropriate number of ventilation is 2.7 for dewatering room with treatment capacity ten thousand per day.

    Reference
    Related
    Cited by
Get Citation

杨鹏,刘雪峰,门玉葵,刘承东.多因素对地下污水厂H2S与NH3浓度的影响[J].土木与环境工程学报(中英文),2018,40(5):124~132