Comparative experimental analysis of capillary radiant cooling on indoor environment
CSTR:
Author:
Affiliation:

Clc Number:

TU831

Fund Project:

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
  • |
  • Comments
    Abstract:

    Tests of capillary radiant cooling system in Chongqing were carried out and thermal parameter were analyzed in conditions of three different capillary laying modes (ceiling, wall and floor) with 18℃ supply water temperature. It concluded that when capillaries were laid on the ceiling, wall and floor respectively, the average temperature of working area was 26.27, 27.22 and 26.57℃ respectively and the radiation surface temperature was 20.96, 21.14 and 22.76℃ in turn. By calculation, the PMV of three conditions was -0.27, 0.32 and -0.2 PPD results were 7.06%, 7.47% and 6.34% respectively. It illustrated that all three laying ways at this experimental conditions could meet the air temperature requirements (no more than 28℃) and PMV, PPD attain thermal environment category I.

    Reference
    Related
    Cited by
Get Citation

梁秋锦,陈金华,段坤林,孙海,韩浩然,宋静.毛细管网供冷室内环境对比实验研究[J].土木与环境工程学报(中英文),2019,41(4):185~192