An Improved Method of the Transient Waveform Analysis in Power Systems
Article
Figures
Metrics
Preview PDF
Reference
Related
Cited by
Materials
Abstract:
The angular frequency and decaying constant of each copmonect for the transient waveform in power systems were obtained by using the discrete Fourier transform; the amplitude and phase angle were calculated in the linear curve fitting method. And all of the parameters obtained above were treated in an unified optimization by using the curve fitting optimization of the least square method of general nonlinear funcrion so as to get the results of waveform analysis. Two examples are included.