An Attentive Problem of 35 kV Power Lines in Mountain Area on Protecting Against
Article
Figures
Metrics
Preview PDF
Reference
Related
Cited by
Materials
Abstract:
To counteract capacitive current and resume power system, the neutral point of 35 kV power system at the mountainous area is grounding through the arc winding widely. In fact, there is great difficult in selecting the arc winding to satisfy the requirement of system. In a 35 kV power system which neutral point is grounding through the arc winding, the capacitance current are measured in site when a single-phase is grounding. From the measure data, the imbalance of three-phase voltage whether the arc winding exist or not and the operating situation of arc winding are discussed, and bring forward an attentive problem about operation of arc winding and decrease of lightning outage rates.