Abstract:The application of non-linear load produces a mass of harmonics. The AC voltage meter and the AC current meter used in power system are usually rectifying instruments, which adopt principle of responding to the average value of voltage and current and get the virtual value by using of the proportion between the average value and it. Because they are designed based on the 50 Hz standard sinuous wave, the principle error will occur when the voltageof power system and the current of loads include harmonic. Based on their working principle, this kind of error is analyzed quantificationally. And the result shows that it can not be neglected. The voltage and current meters with real virtual value are proposed.