    Widely concerns of the influence of the HVDC system on the Three Gorges power station have been shown so far. Based on the understanding of the mechanism of the non-characteristic harmonics introduced by HVDC system, the influence of interharmonics on the shaft of hydro-generator unit is studied. A MATLAB simulation model for the Three Gorges hybrid AC and DC transmission system with considering the effect of generator-unit shaft is established. Through time-domain simulation, the influence of the minor-associated component of interharmonics on the generator-unit shaft is analyzed, which arise from the asynchronous operation of the HVDC system. Also, the complex torque coefficient method in frequency-domain is used to analyze this problem. Same conclusions can be drawn from the results of timedomain and frequency-domain analyses.