Experimental Study on Refrigeration Performance of Fin-tube With Circular Hole Under the Frost Condition
Article
Figures
Metrics
Preview PDF
Reference
Related
Cited by
Materials
Abstract:
The performance of heat transfer of fin-tube with circular hole is better than fin-tube without hole if there is no frost,but what is the situation if under the frost condition.Tthe comparison study on performance of heat transfer and refrigeration is carriedout under the frost condition for the heat exchanger with three kinds of fins: circular and half circular hole,circular hole,plane form.The experiment process is finished through the refrigeration system of icebox.In the course of experiment,the influence of frost process to the diameter of circular hole;is analyzed The real refrigeration amount,heat transfer coefficient and real refrigeration coefficient of the three kinds of fins are compared;compare the effect of energy saving of enforced fins is given.The fin efficiency is calculated method and make out the real convection coefficient to disclose the situation of heat transfer of fins is lnade out.Results: compared with plane form fin,the following results are for fin-tube with circular hole: average heat transfer coefficient rise 11.53%,convection coefficient rises 18.84%,real refrigeration coefficient rises 6.83%,virtual refrigeration amount rises 6.02%,electricity saving is 6.39%.Fin-tube with circular hole is the best form for the three kinds of fins.