Comparison of DC Pollution Flashover Performance of Various Types of Long String Insulators
Article
Figures
Metrics
Preview PDF
Reference
Related
Cited by
Materials
Abstract:
With the development of EHV/UHV DC transmission projects, it is inevitable to study DC pollution flashover performance of long insulator strings. The DC artificial pollution tests of five types of porcelain and glass insulators have been carried out in the artificial climate chamber. The paper analyzes the relationship between 50% flashover voltage U50 and string length, the relationship between U50 and salt deposit density, flashover voltage gradients and valid creepage distances of DC polluted insulators. Based on the test results of insulator strings of 5 - 23 units, there are linear relationship between the 50% DC flashover voltages and string length. The experimental results show that the pollution flashover performances of various types of insulators are different, and that the pollution degree exponents of polluted insulators are affected ainsulator materials and shapes, whose values are 0.3 to 0.36. Under the same pollution degree, the pollution performances of glass insulators have advantage of those of porcelain insulators with the same configuration and the flashover voltage gradient along creepage distance and valid creepage distances of glass insulators are higher than those of porcelain insulators.