Heat transfer performance of heat pipe rotating about parallel axes
Article
Figures
Metrics
Preview PDF
Reference
Related
Cited by
Materials
Abstract:
We conducted an experimental study of heat pipe rotating about parallel axes. The entire pinfin of noncontact thermal resistance was used in the cooling section of the heat pipes. The experimental liquidfilled volume range from 10% to 25%, and heat flux density range was 7×103W/m2 to 5.3×104 W/m2. A cooling current of air was formed by the heat pipe rotation. The Reynolds number range was 2.3×103 to 1.2×104. The experimental results indicate that the heat transfer performance of the heat pipe was the best when liquidfilled volume reached 20%. The heat transfer capability strengthened gradually along with the increasing rotational speed. The change of the heat power had little impact on the heat transfer performance of the heat pipe. It was found that the absorption liquid core was of little use to the heat transfer performance of the heat pipe. Under the same conditions, the heat transfer performance of the parallel rotating heat pipe was 1.5 times that of coaxial rotating heat pipe.