Limitation and improvement of the equivalent capacity method for calculating the energy loss of distribution networks
Article
Figures
Metrics
Preview PDF
Reference
Related
Cited by
Materials
Abstract:
Through the analysis of the equivalent resistance method, a limitation of the equivalent capacity method was presented. When the direction of power at the feeder source end was changing, the equivalent capacity method for handling small generations would produce a large power loss calculation error. An improved calculation method, one not based on a single equivalent resistance, was proposed. In this method, one day was divided into several periods (such as 24 h), so that the direction of power at the feeder source end for each period does not vary. The equivalent resistance and energy loss in each period were calculated. The sum of all energy losses provided the daily energy loss total. Numerical examples were used to verify the improved method.