Abstract:
Four typical physical models for the internal insulation defects of 110kV cable joint are designed, while the test platform for Partial Discharges (PD) research on cable joint is constructed. A large number of PD data under different models are obtained by inner broadband ring sensor. The statistical analysis on the PD pattern indicates that there are significant differences between four PD forms on the statistical characteristics such as the phase distribution, skewness, kurtosis and degree of asymmetry, which can be used as effective features to reflect different characteristics of PD. Surface discharge and conductive particles may cause more serious damage to the insulation performance of cable joint, so high precaution should be paid on site operation.