Characteristics of UHF partial discharge signal waveforms of typical insulated defects in GIS
CSTR:
Author:
  • Article
  • | |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • | |
  • Comments
    Abstract:

    In order to analyze the discharge features of different insulation defects in various experimental conditions, according to characteristics of partial discharge (PD) from the insulation defects in gas insulated switchgear (GIS)) and using ultra high frequency (UHF) method, a lot of PD experiments are carried out based on the designed four typical physical models of insulation defects of GIS in the simulation device, and the real samples of UHF PD waveforms are recorded. The features of UHF PD waveforms in the different situations are discussed and analyzed in detail, which include different sizes or positions of the physical models or under the different voltages and so on. The results show that in low voltage, regardless of types of UHF electromagnetic wave excited by PD sources, the shapes of PD waveform changed little before the changes of waveform. The remaining time is about several nanoseconds.

    Reference
    Related
    Cited by
Get Citation

唐炬,谢颜斌,周倩,张晓星.气体绝缘组合电器内绝缘缺陷超高频局部放电信号特性[J].重庆大学学报,2009,32(10):1138~1143

Copy
Share
Article Metrics
  • Abstract:
  • PDF:
  • HTML:
  • Cited by:
History
  • Received:May 20,2009
Article QR Code