Analysis on the effect of substation structure on grounding grid corrosion diagnosis
CSTR:
Author:
  • Article
  • | |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • | |
  • Comments
    Abstract:

    The measured data of grounding grid corrosion diagnosis are often influenced by steel structural frames, and thus the diagnosis is inaccurate. Based on grounding grid corrosion diagnosis theory, the characteristics of structure frames number, length, layout location and resistance of the influence on the diagnosis result are analyzed by establishing the simulation model. The results show that regardless of the structural frames’ number, layout location and span length, the existence of structural frames reduces the diagnosis sensitivity of fault branch which is near structural frames, making the extent of diagnosed branch corrosion is lower than that without framing. However, the diagnosed corrosion of the branch which is away from the structural frames won’t be influenced. The bigger the resistance of the structural frames connected to grounding grid, the smaller the diagnosis result of interference. Choose the grounding grid branch which has no obvious increase multiples near structural frames as excavation object can improve the diagnostic accuracy.

    Reference
    Related
    Cited by
Get Citation

刘渝根,冷迪,肖磊石,田金虎.变电站构架对接地网腐蚀诊断影响分析[J].重庆大学学报,2013,36(1):92~97

Copy
Related Videos

Share
Article Metrics
  • Abstract:
  • PDF:
  • HTML:
  • Cited by:
History
  • Online: February 25,2013
Article QR Code