Improved control strategy of direct-driven permanent magnet synchronous generator for wind turbine under unbalanced grid faults
CSTR:
Author:
  • Article
  • | |
  • Metrics
  • | |
  • Related
  • |
  • Cited by
  • | |
  • Comments
    Abstract:

    An improved unbalanced grid fault ride-through control strategy is proposed to meet the low voltage ride through(LVRT) requirements based on the analysis of power characteristics of a full rated converter for direct-driven permanent magnet synchronous generator(PMSG). According to the power characteristics,the relationship among dc-link capacitor voltage,power absorbed by interface reactors and grid-side power output is studied. The information of grid voltage drops is introduced into generator-side converter control to achieve coordinated control of grid-side converter and generator-side converter. The soft control strategy on dc-link capacitor voltage is adopted to suppress double-frequency active power ripple at the expense of a certain voltage fluctuations which is still within the safety range. The simulation results demonstrate that the proposed control strategy can enhance direct-driven PMSG’s unbalanced grid faults ride-through capability.

    Reference
    Related
    Cited by
Get Citation

庄凯,廖勇,刘刃,姚骏,李辉.直驱式永磁同步风力发电机不对称故障下的改进控制[J].重庆大学学报,2013,36(8):76~84

Copy
Share
Article Metrics
  • Abstract:2421
  • PDF: 8945
  • HTML: 3566
  • Cited by: 0
History
  • Online: August 11,2013
Article QR Code