Analysis of three-phase short-circuit currents contributed by DFIG in hybrid wind farm
CSTR:
Author:
Affiliation:

Clc Number:

Fund Project:

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
  • |
  • Comments
    Abstract:

    With great development of wind power in recent years, it is a trend that doubly-fed induction generators (DFIGs) and permanent magnet synchronous generators (PMSGs) operate together in one wind farm. Because of the differences between transient characteristics of the DFIG and PMSG, the short-circuit current of DFIG could be affected by the PMSG. The short-circuit current of whole hybrid wind farm can not be calculated accurately. In this paper, fundamental-frequency fault model of hybrid wind farm consisting of DFIGs and PMSGs is built. The short-circuit current of the DFIG considering the influence of multiple different wind turbines is deduced. Based on the comparison with short-circuit current of single DFIG, factors and change law of short-circuit currents of DFIG in hybrid wind farm are analyzed and summarized. Short-circuit currents of DFIG under different conditions are analyzed and verified by time domain simulations.

    Reference
    Related
    Cited by
Get Citation

王晓阳,郑迪,杨国生,欧阳金鑫,熊小伏.混合风电场中双馈风电机组三相短路电流分析[J].重庆大学学报,2018,41(9):19~29