Abstract:It is still a major problem for research on online monitor dielectric dissipation factor of high voltage equipment insulation. In the field, new methods are paid attention by researchers especially. At present, there are no methods achieving the satisfactory measurement results. Based on the voltage and current at their respective zero crossed points, this paper proposes the integral measurement method which can be used to measure the dielectric dissipation factor of high voltage capacitive apparatus. The formula for dielectric dissipation factor angle computation is deduced by theoretical analysis and the computation results are achieved by digital simulation. Meanwhile, this paper explains the effect to measurements by system frequency, content of harmonic and zero-drift and draws the relevant error curves. It also proposes the measures to reduce the integral measurement method presented in this paper,which can convert measurement of small signal into that of big signal and accurately measure dielectric loss of capacitive apparatus. It also possesses great anti jamming ability under strong electromagnetic interference environment. The online measurement system can detect the dielectric dissipation factor of high voltage equipment by the integral measurement method.