The main means of the voltage-reactive power control of substation are adjusting the taps of load-tap-changing transformer or the reasonable capacity of parallel compensating capacitors according to the operation condition of substation.The "nine-area control strategy" is widely used to adjust voltage in the stated range and reduce the transmission capability of reactive power for power system at present.By analyzing the existent shortages of nine-area control mode for voltage-reactive power,an adjusting voltage calculation method is put forward,input data of which are the real time data of current,voltage and power of the substation.Then operation decision of voltage-reactive power control method of substation is made.By the simulating analysis,predigesting method of upper system is built,based on which an applied real time calculating model and calculating steps is given.