State Key Laboratory of Transmission & Distribution Equipment and Power System Safety and New Technology, Chongqing University, Chongqing 400044, China; 在期刊界中查找 在百度中查找 在本站中查找
State Key Laboratory of Transmission & Distribution Equipment and Power System Safety and New Technology, Chongqing University, Chongqing 400044, China; 在期刊界中查找 在百度中查找 在本站中查找
State Key Laboratory of Transmission & Distribution Equipment and Power System Safety and New Technology, Chongqing University, Chongqing 400044, China; 在期刊界中查找 在百度中查找 在本站中查找
Transformer oil and insulation paper are the research objects, accelerated aging experiments in laboratory are performed. The infrared spectrums of samples of different aging time are obtained by the FT-RI apparatus. The absorption intensity of insulation paper’s stretching vibration of O-H at the wave number of 3 346 cm-1 is weaken with the ageing time, so it can be the characteristic quantity of ageing and it can also be the basis for the on-line monitoring of insulation paper in practical transformers. Transformer oil has C=C and C=O group absorption peak at the wave number of 3006 and 1740 cm-1,and the intensity of the absorption peak became stronger with the aging time. The mid-infrared spectra characteristic of the transformer oil-paper is analyzed. The process and mechanism of transformer oil-paper insulation ageing is explored from perspective of microscopic functional groups.