大型双曲冷却塔的自振特性
作者:
基金项目:

国家自然科学基金资助项目(50608063)


Natural vibration characteristic of large hyperbolic cooling towers
Author:
  • 摘要
  • | |
  • 访问统计
  • | |
  • 相似文献 [20]
  • | | |
  • 文章评论
    摘要:

    针对大型双曲冷却塔的自振特性问题,采用有限元方法进行计算分析,以某典型塔为例分析自振频率和振型的分布特点,并进行冷却塔自振特性的变参数分析,最后拟合得基频和倾覆频率的计算公式。分析表明:冷却塔的基频与混凝土材料参数〖KF(〗E/ρ〖KF)〗、筒体厚度成线性递增关系,与高度成反比,与人字柱总截面面积和子午线退化参数呈二次曲线关系。拟合公式与实测结果吻合较好,说明其在预测冷却塔自振频率方面具有较高可信度。

    Abstract:

    The paper uses the finite element method to study the vibration characteristics of large hyperbolic cooling towers. Taking a typical tower for example, the distribution of the natural frequencies and mode shapes are investigated. The equations to estimate the fundamental frequency and overturning frequency are fitted based on a series of parametric studies. The results show that the fundamental frequency is directly proportional to the concrete material property〖KF(〗E/ρ〖KF)〗 and the thickness of tower wall, and inversely proportional to the height of tower. The fundamental frequency also has a quadratic relationship with the total cross-sectional area of supporting columns and the median regressive parameter. The good matches between the results from the fitting equation and the results from full-scale tests indicate that the fitting equation has a high credibility in predicting the natural frequencies of cooling towers.

    参考文献
    引证文献
    网友评论
    网友评论
    分享到微博
    发 布
引用本文

沈国辉,王宁博,孙炳楠,楼文娟.大型双曲冷却塔的自振特性[J].重庆大学学报,2012,35(2):47-54.

复制
分享
文章指标
  • 点击次数:1596
  • 下载次数: 1141
  • HTML阅读次数: 0
  • 引用次数: 0
历史
文章二维码