Abstract:Reliability non-coherence components (RNC) may exist in a power system due to the effects of distribution substation connection modes, components reliability performance, load level, and other factors. Recognizing RNCs and removing them from a power system can improve system reliability. The reliability non-coherence phenomenon is analyzed and the reliability non-coherence probability, frequency and energy indices, which can describe the degree of the system reliability non-coherence feature, are proposed. Based on the reliability evaluation theory of substation configuration, recognizing technique of RNCs of distribution substation is proposed. The theoretical analysis and example show that the breaker connects high voltage buses may be the RNC when the rated capacity of one transformer can meet the load requirement, and the reliability parameters of breakers have some effects on the reliability non-coherence features of the typical substation configuration.