定形相变材料回填下的地埋管换热器实验
CSTR:
作者:
作者单位:

1.重庆大学 土木工程学院,重庆 400045;2.重庆市地勘局南江水文地质工程地质队,重庆 401121;3.中国三峡建工(集团)有限公司 重庆南岸区广阳岛公司,重庆 400060

作者简介:

周琢(1998- ),男,硕士研究生,主要从事相变蓄能技术研究,(E-mail)kitsch2020@163.com。

通讯作者:

彭清元,男,教授级高工,(E-mail)594541403@qq.com。

中图分类号:

TU83

基金项目:

重庆浅层地温能野外科学观测研究站开放基金资助项目(GCZ-202112)。


Experimental analysis of ground tube heat exchanger with shape-stabilize phase change material backfill
Author:
Affiliation:

1.School of Civil Engineering, Chongqing University, Chongqing 400045, P. R. China;2.Nanjiang Hydrogeological & Engineering Geology Brigade, Chongqing 401121, P. R. China;3.China Three Gorges Corporation Chongqing Nan'an District Guangyang Island Company, Chongqing 400060, P. R. China

Fund Project:

Supported by Open Fund Project of Chongqing Shallow Geothermal Energy Field Scientific Observation and Research Station(GCZ-202112).

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    为研究定形相变材料(SSPCM)作为地埋管回填材料的传热特性,以30 W圆柱形发热棒作为线热源模拟地埋管换热器,用膨胀石墨吸附石蜡制成SSPCM,并将其和普通回填沙以3:7的质量比混合制备成混合回填材料,分析在夏季间歇运行工况下,SSPCM混合回填下的传热特性。结果表明,在短期实验运行模式下,相对普通沙回填,SSPCM混合回填材料形成的温度场优势明显,温度波动较小,管壁附近过余温度差异可达到10 ℃;距离发热中心距离越近,减缓温度场变化的效果越明显;在2种回填条件下,恢复后稳定温度以及恢复所需时间无显著差异;在多周期间歇运行工况时,回填区域内温度明显低于连续运行状况;若运行时间导致的温升超过相变材料潜热利用阶段,SSPCM无法发挥出相变储能的优势。该实验现象对SSPCM实际应用有一定参考价值。

    Abstract:

    To investigate the heat transfer characteristics of a ground heat exchanger(GHE) with shape-stabilized phase change material(SSPCM) backfill, a 30 W cylindrical heating rod was used as a linear heat source in place of the GHE. Expanded graphite adsorbed paraffin was used to create SSPCM, which was then mixed with ordinary backfill sand at a mass ratio of 3:7 to prepare a mixed backfill material. The heat transfer characteristics of the SSPCM mixed backfill material were studied under intermittent operation during summer. The research results indicate that the temperature field formed by the SSPCM mixed backfill material had obvious advantages, with smaller temperature fluctuations. In short-term operation modes, the excess temperature difference near the pipe wall could reach about 10 ℃ when compared with ordinary sand backfill. The effect of alleviating temperature fluctuations became more prominent as the distance from the heating center decreased. There were no significant differences in stable temperature and recovery time after recovery under the two backfill conditions. During intermittent and multi-cycle operation, the temperature in the backfill area was lower than in continuous operation. If the temperature rise caused by running time exceeded the latent heat utilization stage of phase change materials, SSPCM could not fully utilize the advantages of phase change energy storage. These experimental results hold valuable insights for the practical application of SSPCM.

    参考文献
    相似文献
    引证文献
引用本文

周琢,王勇,彭远玲,刘庆功,彭清元,曹聪,周庭正.定形相变材料回填下的地埋管换热器实验[J].重庆大学学报,2023,46(12):106-113.

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2023-03-16
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期: 2023-12-19
  • 出版日期:
文章二维码