Application Analysis of Voltage Unbalance Suppression in Distribution Networks Using Star-delta Transformers
Author:
Affiliation:

1.Youyang Power Supply Branch,State Grid Chongqing Electric Power Company,Youyang County;2.School of Electrical Engineering,Chongqing University,Shapingba District

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    单相负荷用电随机性加剧了低压配电网三相电压不平衡,现有的低压配电网三相负荷不平衡控制措施主要采用换相负荷投切、附加不平衡补偿装置两类,均存在使用大量有源电力电子器件、供电不连续、补偿流程长、系统复杂等不足,使治理三相电压不平衡成为亟待解决的难题。本文提出并分析Y-△联结拓扑结构的功率转移变压器抑制低压配电网三相不平衡的自适应调节的方法,仿真分析了功率转移变压器抑制三相不平衡的原理和影响因素,搭建了基于Y-△功率转移变压器的抑制三相电压不平衡的模拟实验平台,分析了不同不平衡负荷下的电压不平衡抑制规律。并分析了Y-△联结变压器在实际输电线路的应用情况。实验及现场数据表明,基于该方法,无需主动控制,能够自动、实时平衡三相功率,改善三相负载不平衡。

    Abstract:

    The stochastic nature of single-phase loads exacerbates the three-phase voltage imbalance in low-voltage distribution networks, and the existing three-phase load imbalance control measures for low-voltage distribution networks mainly use two types of phase-change load casting and additional imbalance compensation devices, discontinuity of power supply, long compensation process, and complexity of the system, have made the management of the three-phase voltage imbalance a difficult problem that needs to be solved urgently. This paper proposes and analyses the method of adaptive regulation of Y-△ connection topology power transfer transformer to suppress three-phase unbalance in low-voltage distribution network, simulates and analyses the principle and influencing factors of three-phase unbalance suppression by power transfer transformer, builds a simulation experimental platform based on Y-△ power transfer transformer to suppress three-phase voltage unbalance, and analyses voltage unbalance suppression law under different unbalanced loads. The application of Y-△ coupling transformer in actual transmission lines is also analysed. The experimental and field data show that based on this method, without active control, it can balance three-phase power automatically and in real time, and improve three-phase load imbalance.

    参考文献
    相似文献
    引证文献
引用本文
分享
相关视频

文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2024-12-02
  • 最后修改日期:2025-02-17
  • 录用日期:2025-03-18
  • 在线发布日期:
  • 出版日期:
文章二维码